Interconnection Standards   

Last DSIRE Review: 11/06/2012
Program Overview:
State: Washington
Incentive Type: Interconnection
Eligible Renewable/Other Technologies: Solar Thermal Electric, Photovoltaics, Landfill Gas, Wind, Biomass, Hydroelectric, Geothermal Electric, Fuel Cells, Municipal Solid Waste, CHP/Cogeneration, Anaerobic Digestion, Small Hydroelectric, Tidal Energy, Wave Energy, Fuel Cells using Renewable Fuels, Microturbines, Other Distributed Generation Technologies
Applicable Sectors: Commercial, Industrial, Residential, Nonprofit, Schools, Local Government, State Government, Fed. Government, Agricultural, Institutional
Applicable Utilities:Investor-owned utilities
System Capacity Limit:20 MW
Standard Agreement:Yes
Insurance Requirements:"Additional" liability insurance generally not required for net-metered systems. For other systems, requirements vary by system application and/or size; levels established by UTC.
External Disconnect Switch:Generally required for systems up to 300 kW; not addressed for larger systems
Net Metering Required:No
Web Site: http://www.wutc.wa.gov/energy
Authority 1:
Date Enacted:
Date Effective:
Chapter 480-108 WAC
3/6/2006 (subsequently amended)
4/6/2006
Summary:

In September 2007, the Washington Utilities and Transportation Commission (UTC) adopted interconnection standards for distributed generation (DG) systems up to 20 megawatts (MW) in capacity. The revised standards provide for two separate levels of interconnection based on system capacity. The first level applies to systems up to 300 kilowatts (kW). The second level, which applies to systems sized between 300 kW and 20 MW, embraces the Federal Energy Regulatory Commission's (FERC) interconnection standards.* The UTC's standards apply to the state's investor-owned electric utilities -- but not to municipal utilities or electric cooperatives.

All interconnections of systems up to 300 kW must conform to all applicable codes and standards for safe and reliable operation, including the National Electric Code (NEC); National Electric Safety Code (NESC); the standards of the Institute of Electrical and Electronics Engineers (IEEE); the standards of the North American Electric Reliability Corporation (NERC); the standards of the Western Electricity Coordinating Council (WECC); American National Standards Institute (ANSI); Underwriters Laboratories (UL) standards; local, state and federal building codes, and any electrical company's written electric service requirement approved by the UTC.

With utility approval, interconnection to spot networks and area networks is permitted for systems up to 300 kW. A UL-approved safety disconnect switch is generally required. However, this requirement may be waived if a customer (1) demonstrates, to the satisfaction of utility, that a system will perform physical disconnection of the generating equipment supply internally, and (2) agrees that service may be disconnected entirely if the system must be physically disconnected for any reason. Utilities have the authority to review the need for a dedicated distribution transformer. If such equipment is necessary, the customer must pay for the costs. Systems eligible for net metering do not require additional liability insurance. However, utilities are authorized to require additional insurance and indemnification for systems ineligible for net metering (but not greater than 300 kW).

Utilities must have a designated point of contact for customers seeking to interconnect systems up to 300 kW, and must file with the UTC a standard form application and a model interconnection agreement. Application fees are limited to $100 for systems up to 25 kW, and $500 for systems greater than 25 kW but not greater than 300 kW. The UTC's rules include provisions for dispute resolution.

For systems sized 300 kW to 20 MW, utilities must offer service equivalent in all procedural and technical respects to the interconnection service the utility offers under the small generator interconnection provisions of its open access transmission tariff (OATT) as approved by the FERC. The FERC's standards for systems up to 20 MW provide for three levels of interconnection. (However, the first level -- the 10-kW inverter process -- does not apply in Washington, because these smaller systems are covered by the rules described above.) The UTC could approve an alternative proposal if a utility demonstrates that the FERC's interconnection standards will impair service adequacy, reliability or safety, or will otherwise be incompatible with the utility's electric system.


* In general, the FERC's interconnection standards for DG systems up to 20 MW apply to facilities that connect at the transmission level. State-level interconnection standards generally govern interconnection at the distribution level.


 
Contact:
  Steve Johnson
Washington Utilities and Transportation Commission
1300 South Evergreen Park Drive, S.W.
P.O. Box 47250
Olympia, WA 98504-7250
Phone: (360) 664-1346
E-Mail: sjohnson@utc.wa.gov
Web Site: http://www.wutc.wa.gov
NCSU - home
Disclaimer: The information presented on the DSIRE web site provides an unofficial overview of financial incentives and other policies. It does not constitute professional tax advice or other professional financial guidance, and it should not be used as the only source of information when making purchasing decisions, investment decisions or tax decisions, or when executing other binding agreements. Please refer to the individual contact provided below each summary to verify that a specific financial incentive or other policy applies to your project.

While the DSIRE staff strives to provide the best information possible, the DSIRE staff, the N.C. Solar Center, N.C. State University and the Interstate Renewable Energy Council, Inc. make no representations or warranties, either express or implied, concerning the accuracy, completeness, reliability or suitability of the information. The DSIRE staff, the N.C. Solar Center, N.C. State University and the Interstate Renewable Energy Council, Inc. disclaim all liability of any kind arising out of your use or misuse of the information contained or referenced on DSIRE Web pages.

Copyright 2012 - 2013 North Carolina State University, under NREL Subcontract No. XEU-0-99515-01. Permission granted only for personal or educational use, or for use by or on behalf of the U.S. government. North Carolina State University prohibits the unauthorized display, reproduction, sale, and/or distribution of all or portions of the content of the Database of State Incentives for Renewables and Efficiency (DSIRE) without prior, written consent.